IQ8Quad Ex (i) rate of heat rise detector - 803271.EX.F0

  • Brand : ESSER
  • Product type : Detectors for hazardous areas
  • Category : Network and Telecom
  • Model :803271.EX.F0
  • Max. Input Voltage (Ui) : 21 V DC
  • Max. Input current (Ii) : 252mA
  • Max. Output current (Io) : 10mA
  • Internal capacity Max. (Ci) : 1nF
  • Ambient temperature (Ta) : -20°C ... 70°C
  • Category II 2G (with Ex safety barrier article No. 764744)
  • Explosion protection Ex ib IIC T4
  • Operating voltage : 8 ... 42 V DC
  • Quiescent current : @ 19 V DC 40 μA
  • Alarm current : @ 9 V DC 18 mA
  • area max. surveillance : 30 m²
  • Max height surveillance : 7.5 m
  • Air velocity : 0 m/s ... 25.4 m/s
  • Operating temperature: -20°C ... 50°C
  • Storage temperature : 25°C ... 75°C
  • Relative humidity : < 95%
  • Protection index : IP43 (with base + option)
  • Material : ABS
  • Colour : white like RAL 9010
  • Weight : approx. 110g
  • Certification according to EN 54-5 A1R : 2002
  • Dimensions : Ø: 117 mm H: 49 mm (including base 62 mm)
  • Declaration of performance DoP-20913130701
In stock
SKU
GLO803271.EX.F0CM
ESSER Detectors

Guarantee safe & secure checkout

Choose the IQ8Quad Ex (i) - 803271.EX.F0 rate-of-rise heat detector at a low price.

The rate-of-rise heat detector guarantees reliable detection of fires with high heat release. It has a built-in thermostatic function guaranteeing fire detection with a slower temperature rise.

This inexpensive ESSER 803271.EX.F0 fire detector can be used especially for areas at risk of explosion. It can also be used as a conventional detector with 764744 intrinsic safety barrier, or as an addressable detector with 804744 intrinsic safety barrier.

Treat yourself to the IQ8Quad Ex (i) - 803271.EX.F0 rate-of-rise heat detector at the best price on the market and discover many other products in the Esser category on Glotelho.cm, the leader in online sales in Cameroon.

Specifications of the 803271.EX.F0 rate-of-rise heat detector:

  • Brand : ESSER
  • Product type : Detectors for hazardous areas
  • Category : Network and Telecom
  • Model :803271.EX.F0
  • Max. Input Voltage (Ui) : 21 V DC
  • Max. Input current (Ii) : 252mA
  • Max. Output current (Io) : 10mA
  • Internal capacity Max. (Ci) : 1nF
  • Ambient temperature (Ta) : -20°C ... 70°C
  • Category II 2G (with Ex safety barrier article No. 764744)
  • Explosion protection Ex ib IIC T4

IQ8Quad Ex (i) rate of heat rise detector - 803271.EX.F0